Acti9 iC60N miniature circuit breaker, 1P 16 A C curve — A9F74116

Reference: A9F74116

Schneider Electric modular protection: one protected pole, 16 A, C curve and 18 mm width. Icn 6 kA at 230 V AC under EN/IEC 60898-1.

Range
Acti9 iC60N
Pole configuration
1P — 1 protected pole
Rated current
16 A
Build your quotationTailored quotation

Price, packaging and lead time confirmed for your quantity and destination.

View my selection and send the enquiry ↗

The product in detail

Schneider Electric A9F74116 is an Acti9 iC60N miniature circuit breaker for overload and short-circuit protection. It has one protected pole, a 16 A rating and a C tripping curve. The 18 mm modular body clips onto a 35 mm DIN rail.

Its Icn breaking capacity is 6,000 A at 230 V AC under EN/IEC 60898-1. The Icu value is 10 kA at 220 to 240 V AC under EN/IEC 60947-2. The official product data sheet specifies the applicable voltages and standards for selecting circuit protection.

Request a quotation from MWB TRADING using reference A9F74116, the required quantity and destination country. Include the supply voltage and switchboard requirements to confirm the associated equipment.

Applications

  • Circuit protection against overloads and short circuits
  • DIN rail modular power distribution

For a tailored quotation

Select the rating and curve for the circuit, then verify prospective short-circuit current and protection coordination. Quote A9F74116, quantity and destination in your enquiry.

Contact our team ↗

Specifications

Acti9 iC60N miniature circuit breaker, 1P 16 A C curve — A9F74116
BrandSchneider Electric
ReferenceA9F74116
RangeActi9 iC60N
Pole configuration1P — 1 protected pole
Rated current16 A
Tripping curveC
Trip unit technologyThermal-magnetic
Icn breaking capacity6,000 A at 230 V AC — EN/IEC 60898-1
Icu breaking capacity10 kA at 220–240 V AC — EN/IEC 60947-2
Rated insulation voltage Ui500 V AC, 50/60 Hz — EN/IEC 60947-2
Impulse withstand voltage Uimp6 kV — EN/IEC 60947-2
Frequency50/60 Hz
Mounting35 mm DIN rail
Width18 mm
Height85 mm
IP protectionIP20; IP40 in a modular enclosure — IEC 60529
Operating temperature−35 to +70 °C
Operating altitude0 to 2,000 m
StandardsEN/IEC 60947-2; EN/IEC 60898-1